Thermal Imaging Data
Thermographer H.J. Tittel, E.E.
Equipment P24-0751, E24-0506, M24-0516,
  Return from Soap Tank Liquor
  Pump
Location Client
Date xx/xx/03
Time 1:41:21 PM
Background Temp. 80°F
   
Analysis & Problem Classification
Hot Spot 167.9°F
Reference Temp. 126.1°F
Difference 41.8°F
Classification C
Thermographer's Notes Review Fuse Holder Connections
  & Cables for Damage. Review
  Fuse Application. Replace