| Thermal Imaging Data |
| Thermographer |
H.J. Tittel, E.E. |
| Equipment |
P24-0751, E24-0506, M24-0516, |
| |
Return from Soap Tank Liquor |
| |
Pump |
| Location |
Client |
| Date |
xx/xx/03 |
| Time |
1:41:21 PM |
| Background Temp. |
80°F |
|
|
 |
|
| Analysis & Problem
Classification |
| Hot Spot |
167.9°F |
| Reference Temp. |
126.1°F |
| Difference |
41.8°F |
| Classification |
C |
| Thermographer's Notes |
Review Fuse Holder Connections |
| |
& Cables for Damage. Review |
| |
Fuse Application. Replace |
| |
Cable as Needed. |
|